Passive fire protection and the importance of limiting temperature for steel structure

download a pdf

What is a limiting temperature or critical temperature of a steel structure?

The strength of steel at high temperature is well understood and documented. It is known that at a temperature above 500°C, hot rolled structural steel loses a significant amount of its ambient temperature load capacity.  

Steel frame structures can be designed so that the maximum stress on the steel members is limited to 60% of their individual maximum capacity at ambient temperatures. This additional 40% redundancy provides the frame with strength in abnormal situations, such as a fire. Dependant on the size, shape and orientation, this additional capacity may equate to a calculated collapse temperature of 550°C, rather than just above ambient. This means that above 550°C, the structural steel member doesn’t have enough strength to support the structure it is maintaining. This is the limiting or critical temperature.  

  • If the steel is utilised more than 60%, the limiting temperature reduces.
  • If the steel is utilised less than 60%, the limiting temperature increases.

To know more, have a look at this graph showing temperature versus time in a actual firetest...

How does the intumescent coating react to fire?

From the example above, if 550°C is the limiting temperature before the structure collapses, the graph below demonstrate the typical temperature profiles:

  • BS EN 1363-1 heating curve,  
  • a steel section protected by an intumescent coating, in green  
  • an unprotected steel section, in red.

The intumescent coating doesn’t really start to protect significantly until around 250-270°C, which is commonly about ten minutes after the fire starts.

This is where we can first see a reaction. That’s linked to the chemical reaction of the intumescent coating, converting from a paint film to an insulating char.

[Translate to English (GB):] Fire testing Intumescent coating Nullifire
[Translate to English (GB):] Nullifire Fire testing Intumescent coating

Once the char is in place, it begins to insulate at a lower rate, slowing the build-up of heat in the steel core. The slight curve is generally the same shape regardless of the thickness of the intumescent, but the thicker the coating, the more elongated the green curve. This equates to the more time to reach the limiting temperature. The extra time needed divided by the difference to Critical Core Temperature (CCT) is a factor in the protection thickness requires.  

For example:

  • For 60 minute protection with a limiting temperature of 350°C:
  • To add 50 minutes to protect an additional 80°C of temperature (based on 270°C completed reaction) = 50/80 = 0.625

Another example:  

  • For 60 minute protection with a limiting temperature of 750°C:
  • Additional 50 minutes to protect an additional 480°C = 50/480 = 0.104

Why is the thickness need lower at a higher temperature?

This is not an absolute value, but a demonstration that approximately 6x more intumescent is needed to protect the same piece of steel for 60 minutes if the limiting temperature is 350°C, compared to if it was 750°C. This is protecting with the same coating.  

On all Nullifire intumescent coatings there are tables to give you the correct assessed protection requirements. The tables don’t always show this factor of six as demonstrated above because the performance is not always linear as the example suggests.  

Performance varies for every product, over different substrates, and over different fire resistance periods - which is why performance can’t be modelled. Performance must always be tested and assessed.  

Why is the critical temperature important in steel protection?

To understand with the critical temperature is important, you should keep in mind this information:

  • 350°C could be the failure temperature if the steel is very highly utilised, used to almost the limit of its capability. There is not much extra strength to resist any heating above ambient.  
  • 750°C could be the failure temperature when the steel is very underutilised. There is a lot of extra strength to resist the additional heat increase.  
  • The actual design of the building and the principles used dictate the actual limiting or critical temperature of the steel structure. If the steel utilisation is known, it can be calculated. If it unknown, the country building code default limiting or critical temperature must be used.

Only a trained and competent person, such as a structural and/or fire engineer, can determine the limiting or critical temperature of structural steel based on the steel dimensions, length, strength, loading and orientation, etc.  

Using the protection thicknesses for a limiting temperature of 650°C and higher, without understanding the actual steel utilisation or loading, may significantly under protect the structural steel frame. The fire protection will not be installed to the required level.  

Passive fire protection
Structural steel
Intumescent coatings
https://www.nullifire.com/en_GB/technical-zone/knowledge-hub/the-importance-of-limiting-temperature/
visit their website

More articles

Fire protection of concrete-filled, hollow structural steel

Filling of closed profile or structural hollow sections with concrete is a well-known practice in the structural design of buildings.

It offers several advantages over unfilled hollow sections, such as cost versus strength optimisation, durability and aesthetics, increased fire resistance and much more, but it needs to be done correctly.

Passive fire protection
Structural steel
learn more

The importance of getting it right

KTA-Tator are a North American company specialising in the testing of steel and concrete structures. With over 70 years' experience they have amassed a sizable body of knowledge, making them one of the leaders in third-party testing in the USA.

One of their consultants, Jay Helsel, recently posted a case study, reporting on the findings of their investigations into the failure of intumescent coatings applied to a project in a north-eastern, coastal location in continental USA.

Intumescent coatings
Passive fire protection
learn more

Passive fire protection of steel structures

A look at the legal or regulatory requirements for passive fire protection of steel structures in Australia, written by John Rakic, Managing Director of Trafalgar Fire.

John discusses the requirements of our own National Construction Code (NCC) encompassing fire testing requirements of AS1530 Part 4 or an equivalent fire test method, along with the strict requirements contained in AS4100 for data analysis and calculation of the thicknesses of fire protection materials required to provide a compliant FRL.

Passive fire protection
learn more

Fire stopping of service penetrations

There are many means through which heat can move from the fire side of a barrier to the non-fire side of a barrier. The fire barrier and/or the fire stopping material(s) themselves can (and do) get hot on the non-fire side in a fire, so choice and construction of fire barriers are important and differ depending on the fire rating duration.

This article assists in making those choices.

Passive fire protection
learn more

product datasheet library

We maintain a library of product datasheets as a ready-reference for you. This library is updated regularly but there are many products available so it isn't possible to provide every datasheet available. We do aim to provide the majority of datasheets for most the popular products.

visit the intumescent paint products datasheet library

still can't find what you're looking for?

If you can't find what you're looking for please let us know.

We aim for this website to be a comprehensive source of knowledge for intumescent coatings professionals or anyone with an interest in the subject.

We'll let you know via email when your request has been answered.

Thanks... we'll get back to you soon.
Sorry... there's been a problem. Please call us if it continues.

engineering portal

architecural portal